Estimate annual dry cooler fan energy by multiplying the electrical input power in each operating condition by its duration and the number of fans running, then adding the results. The power must match the actual duty. A nominal wattage multiplied by every hour of the year is not automatically an estimate of real consumption.
This guide separates measured fan performance from assumed operating hours. The worked example uses documented W3G910-KU25-03/F01 performance points and an illustrative annual schedule. It is a calculation method, not a customer case, a predicted cooling profile or a claimed energy saving.
Decide whether the calculation covers fan electrical input only or the complete heat-rejection system. Pumps, external controls and other equipment should not be silently included in a fan-only result. If a meter covers the entire dry cooler circuit, identify its loads before comparing that reading with single-fan performance data.
Distinguish stopped, powered standby and disconnected states. A stopped EC fan can still be energized, and a zero speed command does not establish zero input power. Add measured standby and auxiliary energy wherever they are part of the chosen boundary.
For example, W3G910-KS35-03/F01 has nominal maximum-load input data of 1,770W. Its separate optimum-efficiency data give 1.55kW at the associated reference point. These describe different conditions; neither is a universal power value for every hour of operation.
Prefer real electrical input measurements paired with fan states and the operating duty. Where suitable measurements are unavailable, use manufacturer selection data for the matching airflow, pressure, speed and supply. Keep nominal, free-air and optimum-efficiency figures in their own context.
Do not infer input power from RPM or a control percentage alone. A speed-based estimate needs its assumptions and validation, while a command percentage can depend on configured input scaling. For a purchasing decision, compare the required duty and the corresponding input rather than assuming that a lower nameplate rating means a lower annual bill.
Group the expected or logged operation into conditions with known duration, running fan count and input per fan. If fans stage independently, the count can change between groups. Where fans in one group run at different duties, split them into separate entries instead of assigning one power to all of them.
|
Profile field |
Record or assumption needed |
|
Operating condition |
Airflow, pressure and actual RPM, or a traceable measured operating state. |
|
Input per fan |
Electrical input in kW at that condition, with its measurement or selection source. |
|
Running fan count |
Number operating at the stated input; separate unequal duties. |
|
Duration |
Hours in that condition without overlap with other time groups. |
|
Other included consumption |
Standby, controls or other loads included in the chosen calculation boundary. |
For a non-leap calendar year, an exclusive schedule for the same installed group should account for 8,760 hours. A partial-year estimate should state its own period. Weather bins can help organize the schedule, but an outdoor temperature alone does not establish fan demand because the liquid load and operating targets also vary.
The following points for W3G910-KU25-03/F01 provide the fan inputs for the example. They use 400V, three-phase supply and 50Hz. Air performance is measured to ISO 5801, installation category A, at an air density of 1.15 kg/m³ ±2%. Pressure is static pressure increase pfs.
|
Measured point |
RPM |
Airflow m³/h |
Pressure Pa |
Input kW |
|
2 |
980 |
29,845 |
80 |
1.938 |
|
6 |
850 |
25,820 |
61 |
1.255 |
|
10 |
700 |
21,260 |
41 |
0.701 |
These are different operating points, not equal airflow duties. The table does not establish when a particular dry cooler can use each one. A project operating profile must separately demonstrate that the required heat rejection is maintained under each proposed condition.
Assume twelve identical fans all run at point 2 for 1,000 hours, point 6 for 2,000 hours and point 10 for 3,000 hours. Assume a further 2,760 hours with no running-fan energy included. These hours and the fan count are teaching assumptions, not manufacturer or site operating data.
Energy in kWh = input per fan in kW × running fan count × hours. This schedule excludes standby and auxiliary consumption.
|
Condition |
Input per fan kW |
Running fans |
Hours |
Energy kWh |
|
Point 2 |
1.938 |
12 |
1,000 |
23,256 |
|
Point 6 |
1.255 |
12 |
2,000 |
30,120 |
|
Point 10 |
0.701 |
12 |
3,000 |
25,236 |
|
No running fans |
Excluded |
0 |
2,760 |
0 |
The calculated running-fan energy is 78,612kWh, or 78.612MWh. Add the measured energy omitted by this boundary to obtain a broader electrical total. In particular, the zero in the final time group is a calculation assumption for running fans, not a statement about the standby input of an energized EC fan.
A meaningful comparison uses a common annual thermal demand and consistent air and liquid conditions. Different fans or control strategies can require different speeds and running counts to meet that demand. Calculate each proposed arrangement from its own matching performance data.
Energy saving is the difference between two justified totals with the same boundary. The example above has no baseline and therefore supports no saving percentage. For a financial evaluation, apply the applicable electricity tariff and include the relevant equipment, installation and commissioning costs. Demand charges or time-varying rates need their own treatment.
Send the existing full fan model, installed quantity, required duties and available operating logs to APAC FAN for selection support. Identify whether power is measured or estimated and which loads the meter includes. For a known-model quotation, send the complete designation, quantity and destination.
The China-made /F01 versions of the two examples have the same performance as their respective base models, allowing the corresponding PDFs to be used. Retain the full /F01 designation in procurement and verify the actual operating configuration.
Explore our ebm-papst supply support and ebm-papst product range for further product options.
Q1: Can annual energy be calculated from maximum-load watts alone?
A1: That produces only a stated assumption about operation at that input. A useful consumption estimate needs the time spent at the relevant operating powers.
Q2: Does a 50 percent fan command mean 50 percent electrical input?
A2: No fixed relationship is established by a command percentage. Use measured input or matching selection data and verify the configured control characteristic.
Q3: Does the example prove a specific energy saving?
A3: No. It calculates one illustrative schedule without a comparison baseline. The hours and number of fans are assumptions.
Q4: Are pumps included in the 78,612kWh result?
A4: No. The example covers running fan input only and excludes pumps, standby and auxiliary loads.
Q5: What is needed for a real annual comparison?
A5: Provide the thermal demand profile, operating hours, fan counts, matching fan duties or measured powers, and a consistent energy boundary for both arrangements.