A dry cooler fan must move the required air volume through the coil and the rest of the air path. Its maximum free-air rating does not establish how much air it will deliver after installation. The useful selection point combines airflow with the pressure the fan must overcome.
This guide explains how to read that point for large ebm-papst EC axial fans. W3G910-KU25-03/F01 provides a measured-data example, while W3G800-KV05-03/F01 illustrates the checks needed before comparing a second candidate. The aim is to prepare a sound fan selection, rather than infer cooling capacity from a catalogue airflow alone.
Obtain the target air volume from the dry cooler or heat exchanger selection. Keep it associated with the design liquid flow, entering and leaving liquid temperatures, fluid composition and entering air temperature. Fan airflow alone cannot define the heat rejection of the complete unit.
Then obtain the air-side pressure drop at that airflow. A coil pressure drop is meaningful only at its stated flow and condition. A value for a clean coil at one air volume should not be applied unchanged to a different flow or to a heavily obstructed coil.
For application and supply options, see our dry cooler fan solutions.
The coil is usually only part of the resistance that the fan has to overcome. Review guards, screens, inlet openings and discharge components in the assembled equipment. Check whether any of these components were already included in the fan test configuration, so that their losses are not counted twice.
Air access also matters. A nearby panel or an abrupt change in the inlet path can alter how air reaches the impeller. A catalogue curve describes its documented test arrangement; the installed fan and coil still need to be assessed together when the geometry differs.
|
Selection input |
What to establish |
|
Required airflow |
Air volume for the complete coil or for the section served by one fan; keep the allocation explicit. |
|
Air-side resistance |
Pressure drop at that airflow, with the coil condition and other air-path components identified. |
|
Pressure definition |
Whether the selection uses static or total pressure, and the matching fan curve definition. |
|
Fan conditions |
Supply, phase, frequency, actual RPM, control configuration, air density and test arrangement. |
A fan curve relates airflow to pressure increase at a stated speed and test condition. The system resistance curve describes the pressure required to move air through the equipment at different flows. Their intersection is the operating point for that fan and system arrangement.
Read airflow and pressure together. Free-air operation is the zero static-pressure point on the relevant curve. It is a different condition from delivering air through a coil with positive resistance. Likewise, a maximum back-pressure entry is not an airflow rating and does not establish the required duty by itself.
Check the pressure symbol and definition before comparing curves. A static-pressure requirement should be evaluated against compatible static-pressure performance; a total-pressure value includes a different pressure basis. Converting units does not reconcile different pressure definitions.
Consider W3G910-KU25-03/F01, a 910mm EC axial fan with a full square nozzle. The following points belong to one 980 RPM curve, not to three different fans or three field tests on a dry cooler.
Conditions for all three rows: 400V, three-phase supply, 50Hz and 980 RPM. Air performance was measured to ISO 5801, installation category A, at an air density of 1.15 kg/m³ ±2%. Pressure is the documented static pressure increase pfs. Values describe the manufacturer test configuration.
|
Measured point |
Airflow m³/h |
Static pressure Pa |
Input power W |
|
1 |
33,630 |
0 |
1,563 |
|
2 |
29,845 |
80 |
1,938 |
|
3 |
25,915 |
150 |
2,245 |
These rows show why 33,630m³/h cannot be used as the delivered airflow at 150Pa. At the documented 150Pa point, the airflow is 25,915m³/h and the input power is 2,245W. The lower airflow and higher input belong to this particular curve; they should not be turned into a universal rule for every fan design.
If an equipment selection calls for 25,915m³/h at 150Pa, the third row is a relevant candidate point under the stated test conditions. It still requires a review of the installed geometry and operating conditions. It is not a guarantee of the liquid outlet temperature or a measurement of a customer installation.
The 800mm W3G800-KV05-03/F01 is another EC AxiBlade option with a square full nozzle. Its nominal size does not tell you how it compares with the 910mm model at the same required airflow and resistance.
For a valid comparison, establish one target duty and find the speed each candidate requires to meet it. Compare input power and acoustic data at those respective operating points, using a consistent supply and pressure definition. Matching a control voltage alone does not establish matching RPM or airflow.
The available W3G800-KV05-03 nominal sheet is marked preliminary. Obtain confirmed selection data before using it for a final numerical comparison. Until then, it can remain a candidate without being ranked above or below the 910mm model.
APAC FAN supplies the China-made /F01 versions of these two models with the same performance as their respective base models. The corresponding base-model PDFs can therefore support these examples. Keep the full /F01 designation on the enquiry and order; this equivalence does not make the two different models interchangeable.
A dirty coil or a newly restricted inlet changes the air path. Compare the condition of the equipment with the original selection and record fan command, actual RPM, alarms and relevant temperatures. A fan turning normally does not establish that design airflow is being delivered.
Where cleaning or obstruction removal is needed, follow the dry cooler manufacturer procedure and reassess operation afterward. Raising speed without addressing the restriction may increase power and noise while leaving the underlying problem unresolved. Any revised selection also has to remain within the permitted fan operating range.
Keep water-side and air-side checks separate. Incorrect liquid flow, a changed fluid mixture or warmer entering air can affect the leaving-liquid temperature even when the fan meets its intended air duty. Use simultaneous measurements to avoid attributing every temperature problem to the fan.
Send your required airflow, matching air-side pressure drop, supply and installation limits to APAC FAN for selection support. Include the fan quantity and whether the duty is per fan or for the complete dry cooler. For a known-model quotation, send the full model, quantity and destination.
For further product options, explore our ebm-papst supply support and ebm-papst product range.
Q1: Can I use maximum airflow to size a dry cooler fan?
A1: Use airflow at the required pressure. A free-air maximum describes zero static-pressure increase in the stated test arrangement, rather than the duty through a resistive coil.
Q2: Does coil pressure drop stay the same at every airflow?
A2: No. Obtain the pressure drop at the design airflow and stated coil condition. Use the coil or equipment selection information rather than treating one pressure value as a constant.
Q3: Can static and total pressure be compared after converting units?
A3: Unit conversion alone is insufficient. The pressure definitions and test arrangements must also be compatible.
Q4: Does a larger fan always use less power?
A4: Size alone cannot answer that question. Compare the candidates at the same required airflow and pressure, with documented speeds, supply and installation conditions.
Q5: Do the measured points prove the cooling output of my dry cooler?
A5: No. They describe fan air performance in a test configuration. Complete-unit heat rejection also depends on the coil, fluid circuit, temperatures and installed airflow arrangement.