An ebm-papst axial fan performance curve shows how airflow and pressure relate at a stated speed and test condition. Read the axes first, identify the correct curve, and locate the required airflow and pressure together. Then use the numbered measurement table to read the corresponding speed and electrical input.
APAC FAN supplies ebm-papst axial fans, including the S3G500-AM56-21 EC axial fan used in this guide. The example below follows its 230V, 50Hz curves and measured values. It demonstrates how to read the data; it is not a customer installation case or a replacement approval.
On the example chart, the lower horizontal axis shows airflow qv in m³/h, with CFM on the upper axis. The left vertical axis shows fan static pressure rise pfs in Pa, with inches of water on the right. Use one airflow scale and one pressure scale consistently when locating a point.
Moving right means more airflow. Moving up means more pressure. A value such as 6145m³/h becomes a useful duty requirement only when paired with the pressure the fan must overcome at that flow.
For other data sheets, read the pressure symbol and definition before comparing figures. A total-pressure requirement and a static-pressure curve are not directly interchangeable without accounting for the relevant velocity-pressure component.
Check the complete model, document version and chart heading. This example chart is titled “Air flow 50 Hz”; all 16 table rows use 230V and 50Hz. The chart also identifies an air density of 1.2kg/m³ and a measurement arrangement under ISO 5801, installation category A.
The product’s nominal input frequency is 50/60Hz, but the displayed test data are for 50Hz. Keep that condition attached to the example. Do not relabel the values as 60Hz or multiply them by 60/50.
The four colored curves represent 1420RPM, 1200RPM, 1000RPM and 800RPM. Match them to the n column in the measurement table. The numbers on the graph identify table rows; they are not speed percentages or control voltages. The following examples show a single AC curve first, followed by the EC plot and its speed reading key.
The 4656N is a compact AC axial fan supplied by APAC FAN. Its 230V, 50Hz example uses one performance curve, making it a useful starting point before the four-speed S3G500-AM56-21 chart.

Figure 1. Original 4656N air-performance plot, page 4 of the data sheet approved 22 June 2016. Scales and shading are retained.
Start with the airflow scale in m³/h along the bottom and pressure in Pa on the left. The graph also includes CFM and inches of water, so check the unit labels before reading a value.
To read a duty, choose the required airflow, move vertically to the black curve, then read horizontally to the pressure scale. A value read between grid lines is an estimate, not a tabulated measurement.
The free-air end is near 160m³/h at 0Pa. At positive pressure, follow the curve to read the lower airflow. The gray shading is not defined on this page; no operating-limit meaning is assigned to it here.
Four speed curves with numbered measurement points at 230V and 50Hz. The rising black lines show system-resistance relationships for interpreting intersections; no customer system is represented in this article.
Figure 2. Cropped original plot from S3G500AM5621.pdf, page 5, revision 77360, released 7 March 2013. Curve geometry and point numbering are unchanged.
|
Curve color |
Speed |
Numbered rows |
|
Red |
1420RPM |
1–4 |
|
Blue |
1200RPM |
5–8 |
|
Magenta |
1000RPM |
9–12 |
|
Yellow-green |
800RPM |
13–16 |
Read by number as well as color. Point 7 on the blue curve is the worked example on the next page.
For this exercise, take 6145m³/h at 83Pa as the target duty. These values are taken directly from measurement point 7, so the exercise teaches the reading method without inventing a project requirement.
Step 1. Find approximately 6145m³/h on the lower airflow axis. Follow a vertical line upward.
Step 2. Find 83Pa on the left pressure axis. Follow a horizontal line to the right. The two readings meet near the numbered point 7 on the blue curve.
Step 3. Read row 7 in the measurement table. It gives the exact tabulated values below; the graph provides the visual position, while the table avoids estimating a precise value from line thickness.
|
Field |
Point 7 value |
|
Supply voltage U |
230V |
|
Supply frequency f |
50Hz |
|
Speed n |
1200RPM |
|
Airflow qv |
6145m³/h |
|
Static pressure rise pfs |
83Pa |
|
Electrical input Ped |
413W |
|
Current I |
1.85A |
Step 4. State the result: at the documented test condition, the 1200RPM curve includes 6145m³/h at 83Pa, with 413W electrical input at that measured point.
That is not yet proof of the operating point in an actual machine. The equipment’s system-resistance curve must pass through the same point for that intersection to occur at this speed. The installed air path and operating conditions still need to be checked.
A target duty states what the equipment needs. The operating point is where the fan curve and the equipment’s system-resistance curve intersect. The fan does not independently deliver any combination of airflow and pressure below its highest curve.
On the example plot, point 7 lies on the middle rising black line. At the other speeds, that line meets the numbered points 3, 11 and 15. These intersections help illustrate how one resistance relationship can produce different operating points as speed changes. They are not measurements of a customer system.
The following rows come from the same rising black line on Figure 2. They illustrate the relationship between speed, airflow, pressure and input power for the plotted intersections.
|
Point |
Speed RPM |
Airflow m³/h |
Pressure Pa |
Input W |
|
3 |
1420 |
7315 |
117 |
696 |
|
7 |
1200 |
6145 |
83 |
413 |
|
11 |
1000 |
5125 |
57 |
239 |
|
15 |
800 |
4100 |
37 |
122 |
As speed decreases across these rows, airflow, pressure and electrical input all decrease. The lower power figures are accompanied by a lower air duty. They do not show an energy-saving percentage for equal cooling performance, and they do not prove that the lowest speed will meet the equipment requirement.
Use the speed that meets the required duty within the fan’s permitted operating conditions. A 0–10V input is described for the S3G500-AM56-21, but this PDF does not map each plotted speed to a particular command voltage. The graph cannot establish that 1200RPM corresponds to a specific voltage or percentage.
Point 1 gives 9245m³/h at 0Pa and 1420RPM. This is the free-air point in the table. At point 4, the same speed gives 6030m³/h at 175Pa. The 9245m³/h free-air value and the 175Pa rating do not occur together.
The nominal-data page calls 175Pa “Max. back pressure.” Do not rename it the shut-off pressure at zero airflow: point 4 has substantial flow, and the plotted curve extends into a higher-pressure region. The highest visible pressure on the graph is not, by itself, permission to operate there.
The plot contains a flattened or turning region toward the left of the curves. Its shape alone does not define a safe continuous operating range. Use the applicable manufacturer limits when assessing operation in that region; this guide does not assign an unverified stall boundary.
The chart describes a defined test arrangement. Filters, coils, guards, inlet obstructions and discharge geometry can change system resistance or create installation effects. A changed air path can move the operating point and alter the installed result. Confirm the duty in the assembled equipment rather than assuming the catalogue free-air value will be delivered through it.
The measured-value table includes electrical input, current and acoustic data for each numbered row. Keep those values attached to that row. At point 7, the inlet sound pressure level LpAin is 62dB(A), while inlet sound power LwAin is 69dB(A). They are different quantities, even though both use an A-weighted decibel notation.
The source specifies its acoustic measurement conditions, including a 1m distance to the fan axis for sound pressure. A published point value is not a guarantee of sound pressure at an arbitrary position in the completed equipment.
APAC FAN supplies the 4656N AC compact axial fan, the S3G500-AM56-21 and other ebm-papst EC axial fans. For a known part, send the complete model, quantity and delivery destination for a quotation. For a new requirement, also provide the target airflow and static pressure, supply and installation details so the enquiry can be reviewed against the relevant product data.
Browse the axial fan range or contact APAC FAN for pricing and delivery information.
Q1: Can I select a fan using maximum airflow alone?
A1: Maximum free-air flow does not describe airflow through a restrictive system. Check the curve at the required pressure and confirm the relevant installation conditions.
Q2: Does a target below the highest curve confirm suitability?
A2: No. Check the available speed or control setting, the intersection with the system-resistance curve and the permitted operating range. Curve position alone does not approve the installation.
Q3: Can I use this 50Hz example as 60Hz performance data?
A3: The example remains a 230V, 50Hz measurement set. The fan’s 50/60Hz input rating does not justify changing the test label or scaling the values. Confirm applicable performance data for the intended supply.
Q4: Does 413W apply whenever the fan runs at 1200RPM?
A4: No. The table gives 413W at point 7. At the same 1200RPM, point 5 gives 327W and point 8 gives 443W. Electrical input depends on the operating point.