Choose a dry cooler fan by the airflow it can deliver against the resistance of the complete air path, then verify electrical supply, installation and controls. Fan diameter and maximum airflow alone do not establish whether a model will meet the cooling duty.
APAC FAN supplies ebm-papst axial fans for dry cooler projects and replacement requirements. EC models are the main focus of our dry cooler range; AC models are less common in these applications. This guide explains how to prepare a useful selection request and assess EC candidates without confusing fan ratings with complete dry cooler capacity.
A dry cooler transfers heat from water or a water-glycol mixture to ambient air through a finned heat exchanger. The fan moves air through the coil while a pump circulates the liquid. Unlike a refrigerant condenser, the dry cooler normally rejects sensible heat from a liquid circuit without condensing refrigerant in that coil.
The required fan performance depends on the heat exchanger and its operating conditions. A fan cannot be assigned a universal cooling capacity in kW independently of the coil, liquid flow and temperatures. Ask the dry cooler or coil designer to define the required airflow and air-side pressure loss for the stated duty.
For an overview of available products and project support, see our dry cooler fan solutions.
Start with the liquid circuit and the design ambient condition. These inputs allow the heat exchanger designer to establish the air duty that the fans must deliver. For an existing unit, retain the original equipment duty and layout as reference points while checking whether the operating requirements have changed.
|
Selection input |
What to provide |
|
Liquid circuit |
Fluid type and glycol concentration if applicable; liquid flow rate; entering and leaving temperatures. |
|
Thermal duty |
Required heat rejection and the design outdoor air temperature at the equipment inlet. |
|
Air duty |
Required airflow and pressure loss through the coil and relevant air-path components. |
|
Equipment layout |
Flatbed or V-type arrangement; fan quantity; drawings; mounting space and service access. |
|
Electrical and control conditions |
Available voltage, phases and frequency; controller interface; required feedback or alarms. |
|
Site requirements |
Operating temperature range, exposure conditions and any project acoustic limits. |
Keep liquid-side pressure drop separate from air-side pressure loss. Liquid-side pressure drop is used in pump and hydraulic design; it is not the pressure value to enter on a fan performance curve. State whether the air-side requirement is for one fan section or the complete unit.
The fan must deliver the target airflow at the resistance imposed by the coil and installation. Use the relevant manufacturer curve at the intended operating speed and supply conditions, with pressure definitions and test configurations that match the selection method. Check the proposed duty against the permitted operating range.
A free-air flow value describes operation at zero external pressure. It does not describe the airflow through a finned coil. Likewise, maximum pressure and maximum airflow are separate limits rather than a combined operating point. Comparing models only by these two headline values can conceal a poor match at the actual duty.
For a multi-fan dry cooler, the equipment designer should allocate the airflow duty across the coil sections and account for the shared air path. Multiplying a single fan free-air rating by the number of fans does not demonstrate installed airflow. Grilles, inlet geometry and other restrictions must be treated consistently with the fan test configuration, without counting the same component twice.
Nominal fan size is a starting point for packaging. Check the complete assembly drawing for mounting-hole positions, housing depth, terminal-box access, guard arrangement and clearance around the inlet and outlet. A change from an 800mm candidate to a 910mm candidate can require changes to the fan deck and surrounding structure.
Flatbed and V-type dry coolers present different coil and inlet arrangements. Trace the actual air path before comparing candidates, including the space below or beside the coil. Confirm airflow direction and permitted installation position for the exact assembly. Use the equipment manufacturer instructions for separation distances and service access.
For rooftop installations, also check whether parapets, screens or nearby units restrict incoming air or return warm exhaust air to the coil. Increasing fan speed cannot be assumed to correct an unsuitable site layout.
An EC fan can use an AC mains supply. The EC designation describes electronic commutation and does not mean that a low-voltage DC supply can power the fan. Check the rated supply range, phases and frequency, then review the wiring and protection requirements for the complete installation.
Compare the existing controller output with the exact fan input and configuration. Confirm any required speed feedback, alarm contact or communication interface. Features available on one EC model must not be assumed for another, and the delivered parameter settings need to suit the equipment control sequence.
Browse the EC axial fan range to identify candidates, then assess the complete model and suffix against your project data.
APAC FAN supplies W3G800-LV05-03/F01, an 800mm EC AxiBlade fan. This China-made version has the same performance as W3G800-LV05-03. Retain the complete /F01 designation when requesting a quotation or placing an order.
Its base-model data specifies 400V three-phase operation, a 380–480V supply range and 50/60Hz frequency. The maximum-load nominal figures are 1190 RPM, 3500W and 5.3A. These figures establish electrical and nominal operating conditions; they do not establish the airflow your dry cooler will receive at its required pressure.
The fan assembly includes guide vanes and has an IP55 protection rating. Review the full dimensional drawing and the suitability of the complete installation, including electrical entries and exposure conditions. The nominal 800mm size is not the overall assembly dimension.
Cold-weather requirements also need careful reading. The documentation permits occasional startup between -40°C and -25°C, while continuous operation below -25°C requires a fan design with special low-temperature bearings. A minimum-temperature headline without this qualification is insufficient for year-round selection.
This example shows why electrical data, mechanical drawings and environmental notes should be reviewed together before the curve is accepted for a project. The remaining selection step is to verify the required airflow at pressure and the intended control configuration.
Depending on the equipment requirements, APAC FAN can also review W3G800-KS39-03/F01 and W3G910-LV12-03/F01 for dry cooler enquiries. Provide the design duty or the existing fan identity so that the relevant drawings, curves and electrical information can be checked.
The three fans below are compared at the same illustrative air duty. Their /F01 China-made versions have the same performance as their respective base models. Retain the complete suffix on enquiries and orders; this confirmed equivalence does not establish interchangeability between different models.
Common conditions are 400V three-phase supply at 50Hz, airflow of 20,000m³/h and static pressure rise pfs of 100Pa. All three source curves state ISO 5801 installation category A and air density of 1.15kg/m³ ±2%. The example duty is an editorial selection exercise rather than a specified customer project.
The published tables do not contain this exact duty for all three fans. The approximate speed and input below are calculated by interpolation between tabulated points and speed curves. They are estimates, not manufacturer measured values or approved selection results.
|
Model |
Estimated speed |
Estimated input |
|
W3G800-KS39-03/F01 |
About 900 RPM |
About 1.35kW |
|
W3G800-LV05-03/F01 |
About 900 RPM |
About 1.35kW |
|
W3G910-LV12-03/F01 |
About 770 RPM |
About 1.10kW |
Speeds are rounded to 10 RPM and input powers to 0.05kW. The rounded entries do not imply identical control commands or verified equal efficiency for the two 800mm models. The 910mm candidate warrants evaluation where a larger assembly can be accommodated, but this estimate alone does not establish an energy-saving result.
Installation category A provides a common test classification, not proof of identical nozzles, accessories or installed airflow. Confirm each complete assembly and obtain a manufacturer selection at the actual design duty before approving a model. No acoustic comparison is inferred from this interpolation.
Before approving a new design or retrofit, agree how performance will be checked on the assembled dry cooler. Record liquid flow and entering and leaving temperatures together with the air temperature at the coil inlet. Check fan commands, actual RPM, electrical demand and any specified acoustic requirements under documented conditions.
Interpret the results against the agreed test duty. A liquid-temperature shortfall can involve the water circuit, coil condition, local inlet air or fan operation. Recording these conditions together helps the equipment team decide which part of the system needs attention.
For a new design, send the required airflow at pressure, equipment drawing, available supply and control requirements to APAC FAN for selection support. Include the liquid duty and design ambient condition if the air duty still needs coordination with the heat exchanger designer.
For a known-model purchase, send the complete model, quantity and delivery destination. For a replacement with an uncertain identity, add a clear nameplate photograph and mounting details. APAC FAN can quote individual replacements and project quantities after confirming the requested supply version.
Explore our ebm-papst supply and support or browse the ebm-papst product range for further options.
Q1: What information is needed to select a dry cooler fan?
A1: Provide the required airflow and air-side pressure loss, available supply, mounting arrangement, controls and site conditions. Liquid temperatures, flow and thermal duty help the equipment designer establish that air duty.
Q2: Can a dry cooler fan be selected by diameter alone?
A2: No. Diameter does not establish airflow at pressure, electrical compatibility or assembly fit. Check the curve, complete dimensions, airflow direction and control requirements.
Q3: Can a 910mm fan replace an 800mm fan?
A3: Only if the redesigned installation and fan performance meet the equipment requirements. Changes to the fan deck, supports, clearances, supply or control system may be needed. It is not a direct replacement based on nominal size.
Q4: Are EC and AC fans both options for dry coolers?
A4: APAC FAN mainly supplies EC axial models for these enquiries, while AC models are less common in this application range. The choice for an existing unit depends on its electrical supply, controls and required performance. An AC-to-EC change requires compatibility checks.
Q5: Does higher fan speed guarantee the required liquid temperature?
A5: No. Liquid flow, coil performance, entering air temperature and the installed airflow all affect heat rejection. Verify the complete operating condition before attributing a temperature shortfall to the fan.